Aide series UPS is the ideal solution for providing stable and reliable power supply for PCs and some electronics in home and office. The user is ensured of high quality power and battery backup during voltage fluctuations and power outages. Through the UPS software, users are able to shutdown a connected computer in the event of a power failure to protect the data and the device.
Features
Microprocessor-based digital control technology
Faster and more accurate processing of data
Wide Input Voltage Range
Aide UPS is capable of handling a wide input voltage range, supplying clean power in extreme circumstances. It has excellent voltage regulation ability with an ultra-wide input voltage range from 80 ~ 150 Vac or 145 ~ 295 Vac.
Built-in AVR
Aide UPS provides stable power to connected devices in unstable power conditions.
It has built-in automatic voltage regulator, safety running in a wide voltage range, reduces the using of battery, prolongs the life of battery, especially suitable for power fluctuations or poor power areas, supplying clean power in extreme circumstances.
Surge protection
Built-in precisely controlled power protection circuit, eliminate the interference of low voltage and surge, thus protecting the equipment against voltage spikes.
Short-circuit and overload protection
A short circuit is an abnormal connection between two nodes of an electrical circuit, and can cause huge damage to the UPS and any equipment attached to it. Aide circuit protection device will protect against potential short circuit damage, overheating, fire or even explosions. Aide is also equipped with overload protection, meaning that the fuse will automatically be triggered when a load exceeds its value. Both protection devices ensure the safety and reliability of the UPS and any equipment that is attached to it.
Auto sensing frequency
Aide UPS uses frequency adaptive technology. When UPS connect to mains with frequency 50HZ or 60HZ, the system will detect the frequency of mains power, and the output frequency will be the same as the detected frequency even when the mains power fails.
High-speed synchronous conversion
Aide system can automatically track the mains phase, to ensure that the inverter output voltage and mains voltage are identical, decrease the transfer time and surge voltage, minimize the interference to electrical equipment.
Cold start capability
In the absence of any AC input, the cold start function allows users to start UPS with batteries, and without any damage to them or the circuits. Users can easily configure the UPS, even if no AC input is available.
Intelligent battery management
· Aide series UPS adopt interactive Design. When mains power is connected, Aide system will automatically charging the battery, even the UPS is OFF, to ensure the battery have enough power. When the mains power fails, Aide system will automatically switch to battery mode to provide sufficient runtime for the load saving data and safety shutdown.
· Aide UPS also be featured with battery temperature compensation to extend the battery life, three-stage charging to shorten recharge time and battery overcharge / over-discharge protections as well.
Intelligent power ON/OFF
· When the mains power is restored after discharge of the batteries, Aide UPS will automatically restart and self-diagnose to ensure the functionality of the UPS system and batteries.
· Aide system can detect load and automatically shut down in the no-load state (Optional). When the load is less than 5%, the system detects that it is under idling/no-load state, it will automatically shut down in about one minute, reduce losses, effectively extending the life of batteries.
User friendly LED and LCD display
The user friendly LED display, which is situated on the front panel of Aide UPS, provides instantaneous information. Aide LCD model have a backlit LCD display for users to observe the UPS status information, load and battery performance.
Advanced multi-platform communications
RS232 / USB communication port (Optional).
What do we get from using management software
· More customized functions.
· Settable battery discharge and low-voltage test. Through this function users can easily see batteries in good or bad condition.
· Timing boot/shutdown for UPS is available.
· Unattended Safe Shutdown by software. AWP Software is able to intelligently save the data and automatically shut down the sever or computer when a power failure occurs. This software allows the UPS to instruct the operating systems to close down a PC when it is running unattended. Users can set the parameters with which to schedule when the computer or server should shutdown, making sure that no significant data is lost and important backups are created.
Alpha Pro Series UPS is on-line double-conversion UPS with advanced full-time DSP control technology and input power factor correction, it is featured with output power factor 0.9 which enable to delivering more stable and clean power without interruption for critical equipment. Besides sufficient runtime as backup power, Alpha Pro extensible model with powerful battery charger can be fitted with external battery packs for longer runtime requirements. In addition to some standard features, like cold start, wide input range, Alpha Pro is also featured with many advanced features, such as auto fan speed control, ABM, ECO mode, frequency conversion mode etc.
Output voltage, output frequency, Bypass mode, ECO mode, battery low voltage and Frequency Converter enable/disable are settable via LCD panel.
Extensible functions and options
EPO function (Optional)
Alpha Pro is equipped with an Emergency Power Off function, providing users with a way of immediately shutting down all output power from the UPS in the case of emergencies such as fire, flood, and overheating equipment.
Optional built-in isolation transformer (Optional)
Built-in power purifying isolation transformer protects the load from even the most damaging power disturbances.
Advanced multi-platform communications
Standard RS232 communication port and RJ45 protection
Optional USB / RS485 /dry contacts card / SNMP / SMS / communication port
Provides clear status of UPS key parameters
Form factor to fit easily into small spaces
Simulates the utility when on battery for optimum device compatibility
Corrects a wide range of input voltage
To provide full power capability to electronic or IT equipment that may have a wide range of leading and lagging power factors
MODEL |
NDC16 |
NDC-RT16 |
NDC24 |
NDC-RT24 |
||
Capacity |
1600 W / 2000 VA |
2400 W / 3000 VA |
||||
Form factor |
Tower |
Rackmount |
Tower |
Rackmount |
||
DC INPUT |
||||||
Rated voltage |
36 V (S) |
48 V |
||||
DC input range (default) |
30 ~ 45 V (S) |
40 ~ 60V |
||||
AC INPUT |
||||||
AC input range (bypass mode) |
0 ~ 121 V / 132 V / 138 V / 144 Vac for 100 V / 110 V / 115 V / 120 Vac ± 10 Vac |
|||||
AC input range (mains mode) |
100 V: 70 ~ 130 Vac 110 V: 80 ~ 140 Vac 115 V: 85 ~ 145 Vac |
|||||
Frequency input range |
50 Hz / 60 Hz (auto-sense), 50 Hz / 60 Hz ± 5% ~ 15% |
|||||
Generator connection |
Available (generator input power is settable) |
|||||
OUTPUT |
||||||
Inverter output range |
100 V / 110 V / 115 V / 120 Vac ± 5% (settable) |
|||||
AC output range (bypass mode) |
0 ~ 121 V / 132 V / 138 V / 144 Vac for 100 V / 110 V / 115 V / 120 Vac ± 10 Vac |
|||||
AC output range (mains mode) |
100 V: 90 ~ 110 Vac 110 V: 99 ~ 121 Vac 115 V: 103 ~ 126 Vac |
|||||
Output frequency |
50 / 60 Hz ± 0.3 Hz (settable) |
|||||
Waveform |
Pure sine wave |
|||||
Inverter efficiency |
Max. 85% |
|||||
Energy saving mode |
Settable (< 3% load) , enter in 80s |
|||||
No-load shutdown |
Settable (< 3% load), shut down in 80s |
|||||
Transfer time |
≤ 10ms |
|||||
THDV |
≤ 5% |
|||||
Protections |
Overload, short circuit (inverter), battery low voltage, battery overcharge, overtemperature |
|||||
Overload time |
120s for 110%, 60s for 125%, 10s for 150% (transfer to bypass mode) |
|||||
Overload time |
60s for 110%, 10s for 125%, 5s for 150% (Shut down directly) |
|||||
Mute |
Automatic mute in 60s or by manual |
|||||
BATTERIES |
||||||
Battery capacity |
12 V / 9 Ah x 3 |
12 V / 9 Ah x 4 |
||||
Charging current |
Standard model (S): 1 A (default) |
Standard model (S): 1 A (default) |
||||
Equalizing |
Single battery 14.1 Vdc (default), 13.6 ~ 15 Vdc adjustable |
|||||
Floating charge voltage |
Single battery 13.5 Vdc (default), 13.2 ~ 14.6 Vdc adjustable |
|||||
Low voltage alarm point |
Single battery 10.8 Vdc (default), 9.6 ~ 13 Vdc adjustable |
|||||
Low voltage shutdown point |
Single battery 10.2 Vdc (default), 9.6 ~ 11.5 Vdc adjustable |
|||||
COMMUNICATIONS |
||||||
USB+RJ45 |
Supports Windows® 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10 |
|||||
SNMP (optional) |
Power management from SNMP manager and web browser (standard with slot) |
|||||
OTHERS |
||||||
Operating temperature |
5°C ~ 40°C |
|||||
Operating humidity |
Relative humidity ≤ 93% |
|||||
Noise level |
≤ 50 dB (1m) |
|||||
Dimensions (WxDxH) (mm) |
144x410x215 (S) |
440x410x132 (S) |
190x467x335.5 (S / H) |
440x410x132 (S) |
||
Packaged Dimensions (WxDxH) (mm) |
236x492x316 (S) |
611x505x235 (S) |
320x592x462 (S / H) |
611x505x235 (S) |
||
Net weight (kg) |
18.5 (S) |
21.3 (S) |
28.1 (S) |
26.7 (S) |
||
Gross weight (kg) |
19.8 (S) |
24.5 (S) |
30.2 (S) |
30.5 (S) |
Eaton 5E adalah product Line Interactive UPS penting yang menawarkan cost efektif dan proteksi power yang dapat diandalkan terhadap padamnya listrik dan kualitas listrik yang buruk. Berita baiknya adalah ukurannya yang kecil sehingga mudah diinstalasikan baik dalam lingkungan bisnis maupun di rumah.
AidePlus series UPS provides guaranteed power with surge protector for PCs and other electronics in home and office. It has more battery backup outlets than ever before, supplying battery backup power during outages and unsafe voltage fluctuations, as well as protection from damaging surges and spikes.
Alpha Pro Series UPS is on-line double-conversion UPS with high power density (Input PF≥ 0.99) and an enhanced output power factor of 0.9. It offers high levels of reliability and protection for IT systems, telecommunications equipment and mission critical systems, ensuring maximum power reliability. In addition to some standard features, like cold start, wide input range, ECO mode, Alpha Pro is also featured with many advanced features, such as auto fan speed control, ABM, configurable switching time, frequency conversion mode, parallelable, powerful battery charger and background software etc.
To continuously monitor and regulating both voltage and frequency
To provide precision logic
For harsh and severe power supply condition
To provide full power capability to electronic or IT equipment that may have a wide range of leading and lagging power factors
Maintaining operating temperature of the system
MODEL |
SDC09 |
SDC27 |
SDC54 |
SDC90 |
SDC-RT18 |
SDC-RT27 |
Capacity |
900W / 1KVA |
2700W / 3KVA |
5400W / 6KVA |
9000W / 10KVA |
1800W / 2KVA |
2700W / 3KVA |
Form factor |
Tower |
Rackmount (Tower Convertible) |
||||
Topology |
Online Double Conversion |
|||||
INPUT |
||||||
Rated voltage |
208 / 220 / 230 / 240VAC |
208 / 210 / 220 / 230 / 240VAC |
208 / 220 / 230 / 240VAC |
|||
Voltage range |
110 - 300VAC (Derating 0 - 100% load) |
110 - 300VAC (Half load) ; 160 - 300VAC (Full load) |
110 ~ 176 Vac (linear derating between 50% and 100% load); 176 ~ 280 Vac (no derating); 280 ~ 300 Vac (derating 50%) |
|||
Frequency |
40 - 70Hz |
40 ~ 70 Hz (auto-sense) |
||||
Power factor |
> 0.99 |
≥ 0.99 |
||||
OUTPUT |
||||||
Voltage setting |
208 / 220 / 230 / 240VAC |
|||||
Regulation |
±1% |
|||||
Frequency |
45-55Hz or 55-65Hz (Mains) ; 50 / 60Hz ±0.1Hz |
|||||
Waveform |
Pure Sinewave |
Sinusoidal |
||||
Crest factor |
3:1 |
|||||
Harmonic |
< 2% (Linear load) : < 5% (Non-linear load) |
≤ 2% (Linear load) : ≤ 5% (Non-linear load) |
||||
Transfer time |
Mains mode to battery mode: 0 ms |
Mains mode to battery mode: 0 ms |
||||
Overload |
105 - 125% : Transfer to bypass in 1min 125 - 150% : Transfer to bypass in 30s > 150% : Transfer to bypass in 300ms |
105 - 125% : Transfer to bypass in 3 min 125 - 150% : Transfer to bypass in 30s > 150% : Transfer to bypass in 100ms |
105% ~ 125%: transfer to bypass in 1 min; |
|||
EFFICIENCY |
||||||
Mains |
> 90% |
> 92% |
> 93% |
≥ 91% |
≥ 92% |
|
Battery |
> 85% |
> 87% |
> 92% |
≥ 86% |
≥ 87% |
|
ECO Mode |
> 95% |
> 97% |
> 98% |
≥ 96% |
≥ 97% |
|
BATTERIES |
||||||
Internal |
3 x 7AH |
8 x 7AH |
16 x 7AH |
16 x 9AH |
4 x 9AH |
6 x 9AH |
Voltage |
36VDC |
96VDC |
192VDC |
48V |
72V |
|
Recharge time |
8hours |
|||||
OTHERS |
||||||
Communications |
RS232, SNMP Slot |
RS232, USB Port, SNMP Slot |
||||
Operating temperature |
0 - 40°C |
|||||
Relative humidity |
0 - 90% (Non condensing) |
|||||
Noise level |
< 50 dB (1m) |
< 58 dB (1m) |
≤ 50 dB (1m) |
|||
W x D x H (mm) |
144 x 336 x 214 |
191 x 464 x 335 |
262 x 580 x 732 |
440 x 658 x 88 |
||
Weight (kg) |
9.5 |
32 |
73 |
74 |
22.73 |
29.26 |
Eaton 5SC UPS menyediakan proteksi line-interactive, terjangkau dan dapat diandalkan untuk server bisnis kecil. 5SC dilengkapi dengan LCD interface untuk real-time status dan pengukuran, dan memberikan output sinewave untuk kompatibilitas terhadap perangkat IT yang sensitif di masa kini.
ArcPure series UPS uses Line Interactive technology and provides a sinusoidal output. It ensures superior protection and a perfectly sinusoidal supply for maximum power continuity and reliability for peripheral network devices, servers, and other electronics in home and office. It has user friendly LCD display. Users can directly know the running situation of UPS through parameters display on the LCD screen. Intelligent monitoring system realizes real-time monitoring of the operating condition / parameters of the UPS system, control UPS running, test and set the power on/off time, and carry out remote monitoring through SNMP card as well.
Alpha Pro RT Series UPS is the high density version of on-line double-conversion UPS with advanced full-time DSP control technology and input power factor correction, it is featured with output power factor 0.9 which enable to delivering more stable and clean power without interruption for critical equipment. Its Rack/Tower convertible design can be fitted to multiple applications, such as telecommunication, storage systems, medical systems, industrial applications especially ideal for blade severs. For critical business continuity applications requiring long runtimes, Alpha Pro RT(extensible model)can be installed with battery extension packs.
with strong load capacity
high reliability and easy maintenance
for higher usability
Input power factor > 0.99, THDi < 3%, environment friendly and high-efficiency and energy-saving
at low load rate: 96% at 40% rated load and 95% at 20% rated load
500KVA system only 1.02 m2 footprint
in on-line mode up to 96%, in ECO mode up to 99%
50Hz / 60Hz frequency anto-sense, adapt to all kind of grid
50Hz input / 60Hz output and 60Hz / input 50Hz output
power factor 0.9, load capability improved 12.5% more than traditional products
support 4 units in parallel
in parallel operation, saving user’s battery cost
and battery configuration setting, battery number 30 ~ 46pcs selectable
Intelligent charge / discharge management and float charging voltage temperature compensation, extending battery lifespan
and utility self boot
easy debugging and test on site
robust self-diagnostic function, and abundant event log for check
7 inches LCD touch screen, friendly human-machine interface
supports RS485 and dry contacts
MODEL |
||
Rated capacity |
450 KW / 500 KVA |
|
INPUT |
||
Input wiring |
3Ph+N+PE |
|
Rated voltage |
380/400/415Vac |
|
Voltage range |
138 ~ 485 Vac (305 ~ 485 Vac without power downgrading; |
|
Input frequency |
40 ~ 70Hz |
|
Power factor |
≥ 0.99 |
|
Current distortion |
< 3% |
|
BATTERIES |
||
Battery voltage |
± 240 Vdc (±180, ± 192, ± 204, ± 216, ± 228, ± 252, ± 264, ± 276 selectable) |
|
Number of battery |
40 pcs12V batteries ( supports 30 / 32 / 34 / 36 / 38 / 42 / 44 / 46 pcs) |
|
OUTPUT |
||
Output wiring |
3Ph+N+PE |
|
Rated voltage |
380 / 400 / 415 Vac |
|
Voltage regulation accuracy |
± 1% |
|
Frequency |
Synchronized with utility in mains power mode: |
|
Power factor |
0.9 |
|
Voltage distortion |
≤ 1% with liner load / ≤ 3% with non-linear load |
|
Crest factor |
3:1 |
|
Inverter overload capacity |
105% < load ≤ 110%: transfer to bypass in 60 min |
|
Bypass overload capacity |
Load ≤ 135% for long term; < 1000% load for 100ms |
|
SYSTEM |
||
Efficiency |
96% |
|
Max. number of parallel |
4 units |
|
Transfer time |
0ms |
|
Protection |
Lack-phase protection, phase-error protection, short circuit protection, overload protection, over-temperature protection, battery low voltage protection, output over / low voltage protection, fans failure protection ect. |
|
Communications |
RS485, dry contacts, SNMP |
|
Display |
7 inches LCD touch screen |
|
OTHERS |
||
Operating temperature |
0 ~ 40°C |
|
Storage temperature |
-40°C ~ 70°C |
|
Humidity |
0 ~ 95%(non-condensing) |
|
Altitude |
≤ 1000m. Above 1000m, derating 1% for each additional 100m
|
|
Protection level |
IP20 |
|
Noiselevel at 1 m |
< 68 dB |
|
Cabinet dimensions (WxDxH) (mm) |
1200x850x2000 |
|
Weight (kg) |
795 |
Eaton 5P terbaru adalah UPS line-interactive 650VA-1550VA generasi baru dengan fitur pengukuran energi dan LCD yang canggih. Eaton 5P adalah UPS sempurna untuk melindungi peralatan jaringan dan IT seperti server, switch, router dan peralatan penyimpanan, dalam bentuk tower atau rack.
Power Management Connectivity | ||
---|---|---|
Network Card-MS Menyediakan pengawasan serta pengaturan secara real time untuk UPS yang berada didalam Network anda. |
||
Relay Card- MS Menyediakan dry-contact interface antar UPS anda dan relay yang terhubung ke computer, termasuk AS/400, dan juga berbagai penerapan industri lainnya |
||
Network and MODBUS Card-MS Menyediakan sistem monitoring UPS jarak jauh yang akurat serta berkelanjutan |
online double-conversion with DSP control
high reliability, easily maintenance
higher reliability of system
for energy saving
50 Hz / 60 Hz auto-sense frequency
50 Hz input / 60 Hz output and 60 Hz input / 50 Hz output
Input power factor > 0.99, input THDi ≤ 3%, output THDV ≤ 5%, output power factor 0.9
load > 10%, efficiency ≥ 90%; load > 50%, efficiency ≥ 93%
flexible charger parameter and battery configuration setting, monitoring battery disconnected on line
in parallel operation or separate battery pack for different UPS
and battery configuration setting, selectable battery number: 32 pcs / 34 pcs / 36 pcs / 38 pcs / 40 pcs
prolong the working life of battery effectively
and mains supply self-starting
5.7 inches LCD touch screen, friendly human & machine interface
in hard and software, robust self-diagnosing, abundant event log for future check
including the first power-on password control, user password control and Maintenance password control
MODEL |
||
Capacity |
72 KW / 80 KVA |
|
INPUT |
||
Rated voltage |
380 V / 400 V / 415 Vac |
|
Voltage range |
204 ~ 242 Vac (load ≤ 50%); |
|
Rated frequency |
50 / 60 Hz (auto-sense) |
|
Frequency range |
40 ~ 70 Hz |
|
Power factor |
≥ 0.99 |
|
Total harmonic distortion (THDI) |
≤ 3% |
|
Bypass voltage range |
Rated output voltage -40% ~ rated output voltage + 20% (settable via LCD) |
|
OUTPUT |
||
Voltage |
380 V / 400 V / 415 Vac |
|
Voltage regulation |
± 1% |
|
Frequency |
Synchronized with utility in mains mode; |
|
Waveform |
Sinusoidal |
|
Crest factor |
3:1 |
|
Total harmonic distortion (THDV) |
≤ 1% (linear load); ≤ 5% (non-linear load) |
|
Transfer time |
0 ms |
|
Inverter overload capability |
102% ~ 127%: transfer to bypass in 10 mins; |
|
Bypass overload capability |
≤ 150%: long time running |
|
BATTERIES |
||
DC voltage |
± 192 V (options: ± 204 V / ± 216 V / ± 228 V / ± 240 V) |
|
Inbuilt battery of standard model |
No |
|
Charging current |
1 ~ 24 A (settable via LCD) |
|
SYSTEM |
||
Efficiency |
≥ 93%, ECO mode 98.5% |
|
Display panel |
5.7 Inches LCD touch screen |
|
Alarm |
Battery mode, low battery, fans fault etc |
|
Max. parallel numbers |
4 |
|
EMI |
EN62040-2 |
|
EMS |
IEC61000-4-2 (ESD) |
|
COMMUNICATIONS |
||
RS232 / RS485 / USB / dry contacts (standard) |
Supports Windows® 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10 |
|
SNMP (optional) |
Power management from SNMP manager and web browser |
|
OTHERS |
||
Humidity |
0 ~ 95% RH @ 0 ~ 40°C (non-condensing) |
|
Noise level |
≤ 60 dB |
|
Dimensions (WxDxH) (mm) |
600x800x1680 |
|
Packaged dimensions (WxDxH) (mm) |
720x920x1820 |
|
Net / Gross weight (kg) |
316 / 376 |
UPS Eaton 5PX Rack/Tower menyediakan daya cadangan line-interactive dan runtime terukur untuk server, sistem penyimpanan, perlengkapan VoIP dan peralatan jaringan. Dengan layar LCD intuitif yang canggih, konsumsi energi turun sampai ke level grup keluaran, dan efisiensi sampai 99%, 5PX adalah UPS yang sempurna untuk melindungi perlengkapan TI modern.
Baterai | ||
---|---|---|
Eaton 5PX 48 R/T EBM 2U 2U Extended Battery Module (EBM) memberikan runtime tambahan untuk UPS Eaton 5PX 1500, 2000 dan 2200 - maksimal 4 EBM dapat disambungkan ke setiap UPS |
||
Eaton 5PX 72 R/T EBM 2U 2U Extended Battery Module (EBM) memberikan runtime tambahan untuk UPS Eaton 5PX 3000 2U – maksimal 4 EBM dapat disambungkan ke setiap UPS |
Power Management Connectivity | ||
---|---|---|
Network and MODBUS Card-MS Menyediakan sistem monitoring UPS jarak jauh yang akurat serta berkelanjutan |
||
Network Card-MS Menyediakan pengawasan serta pengaturan secara real time untuk UPS yang berada didalam Network anda. |
||
Relay Card- MS Menyediakan dry-contact interface antar UPS anda dan relay yang terhubung ke computer, termasuk AS/400, dan juga berbagai penerapan industri lainnya |
||
IBM AS/400 Cable Kabel Antarmuka UPS untuk koneksi UPS ke IBM iSeries/AS 400 |
input power factor up to 0.99
range (190V ~ 485V)
when loads varies
according to the load capacity set by users
for using 14/16/18/20 pcs batteries
miniaturized the complete unit for small footprint
multi-functional keys operation, friendly human-machine interface
for parameters configuration and online updating
90% capacity restored in 4 hours (standard model UPS)
reducing battery discharging times, extending the service life of battery
automatic floating / equalizing charge control, charger dormancy control
from battery mode to mains mode when mains power is restored, reducing the impact on power grid or generator
powerful self-diagnostic function, abundant historical records
EMD environmental sensors
MODEL |
||
Capacity |
27 KW / 30 KVA |
|
INPUT |
||
Rated voltage |
360 V / 380 V / 400 V / 415 Vac |
|
Voltage range |
277 ~ 485 Vac (no derating) |
|
Rated frequency |
50 / 60 Hz (auto-sense) |
|
Frequency range |
40 ~ 70 Hz |
|
Power factor |
≥ 0.99 |
|
Total harmonic distortion (THDI) |
≤ 5% |
|
Bypass voltage range |
-40% - +15% (settable) |
|
OUTPUT |
||
Voltage |
360 V / 380 V / 400 V / 415 Vac (settable) |
|
Voltage regulation |
± 1% |
|
Frequency |
45 ~ 55 Hz or 55 ~ 65 Hz (synchronized range); 50 / 60 Hz ± 0.1 Hz (battery mode) |
|
Waveform |
Sinusoidal |
|
Crest factor |
3:1 |
|
Total harmonic distortion (THDV) |
≤ 2% (linear load); ≤ 5% (non-linear load) |
|
Transfer time |
Mains mode to battery mode: 0 ms; Inverter mode to bypass mode: 0 ms |
|
Inverter overload capability |
102% ~ 125%: transfer to bypass in 10 mins; |
|
Bypass overload capability |
102% ~ 125%: shut down in 20 mins; |
|
BATTERIES |
||
DC voltage |
Standard model: 240 VDC; Long time model: 192 VDC (168 V / 192 V / 216 V / 240 V optional) |
|
Inbuilt battery of standard model |
60x9 Ah |
|
Recharge time |
Standard model: 90% capacity restored in 4 hours; |
|
SYSTEM |
||
Efficiency |
≥ 93%, ECO mode 98% |
|
Display |
LCD + LED |
|
Alarm |
Battery mode, low battery, fans fault etc. |
|
Max. parallel numbers |
6 |
|
EMI |
IEC / EN62040-2 |
|
EMS |
IEC61000-4-2 (ESD) |
|
COMMUNICATIONS |
||
RS232 / USB / RS485 / dry contacts |
Supports Windows® 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10 |
|
SNMP |
Power management from SNMP manager and web browser |
|
OTHERS |
||
Humidity |
20 ~ 90% RH @ 0 ~ 40°C (non-condensing) |
|
Noise level |
≤ 65 dB (1m) |
|
Dimensions (mm) WxDxH |
350x655x732 (H) |
|
Packaged dimensions (mm) WxDxH |
472x780x920 (H) |
|
Net weight (kg) |
65 (H), 235 (S) |
|
Gross weight (kg) |
75 (H), 250 (S) |
UPS Eaton 9130 memberikan kualitas daya online dan runtime baterai terukur untuk server, jaringan suara dan data, sistem penyimpanan, dan peralatan TI. Dengan efisiensi 95% dalam konversi ganda online dan 98% dalam efisiensi tinggi, UPS 9130 mengurangi biaya energi dan memperpanjang usia baterai secara signifikan dengan teknologi ABM. UPS 9130 mempunyai LCD antarmuka pengguna yang terang untuk memudahkan pemantauan.
Baterai | ||
---|---|---|
Eaton 9130 1000 Tower EBM Extended Battery Module (EBM) memberikan runtime tambahan untuk UPS Eaton 9130 1000 Tower sampai 4 EBM dapat dipasang di setiap UPS |
||
Eaton 9130 1500 Tower EBM Extended Battery Module (EBM) memberikan runtime tambahan untuk UPS Eaton 9130 1500 Tower sampai 4 EBM dapat dipasang di setiap UPS |
||
Eaton 9130 3000 Tower EBM Extended Battery Module (EBM) memberikan runtime tambahan untuk UPS Eaton 9130 2000 dan 3000 Tower sampai 4 EBM dapat dipasang di setiap UPS |
||
Eaton 9130 6000 Tower EBM Extended Battery Module (EBM) memberikan runtime tambahan untuk UPS Eaton 9130 5000 dan 6000 Tower - sampai 4 EBM dapat dipasang di setiap UPS |
Power Management Connectivity | ||
---|---|---|
Network and MODBUS Card-MS Menyediakan sistem monitoring UPS jarak jauh yang akurat serta berkelanjutan |
||
Network Card-MS Menyediakan pengawasan serta pengaturan secara real time untuk UPS yang berada didalam Network anda. |
||
ConnectUPS-BD SNMP/Web Card Memungkinkan pemantauan UPS melalui Web atau SNMP |
||
Environmental Monitoring Probe Memungkinkan pengawasan jarak jauh untuk temperature, kelembaban dan dua alat contact lainnya (memerlukan Web / SNMP card) |
||
Relay Card - BD (AS/400 Compatible) Memberikan antarmuka kontak kering antara UPS Anda dan komputer yang terhubung relai, termasuk AS/400, serta berbagai aplikasi industri. |
UPS Eaton 9130 Rackmount memberikan kualitas daya online dan runtime baterai terukur untuk rak server, jaringan suara dan data, sistem penyimpanan, dan peralatan TI. Dengan efisiensi > 95%, UPS 9130 mengurangi biaya energi dengan memuat daya sampai 3KVA dalam rak 2U. UPS 9130 memperpanjang usia baterai secara signifikan dengan teknologi ABM dan mempunyai LCD antarmuka pengguna yang terang untuk memudahkan pemantauan.
Baterai | ||
---|---|---|
Eaton 9130 1000 Rack EBM 2U Extended Battery Module (EBM) 2U memberikan runtime tambahan untuk UPS Eaton 9130 700 dan 1000 rack sampai 4 EBM dapat dipasang di setiap UPS |
||
Eaton 9130 1500 Rack EBM 2U Extended Battery Module (EBM) 2U memberikan runtime tambahan untuk UPS Eaton 9130 1500 rack sampai 4 EBM dapat dipasang di setiap UPS |
||
Eaton 9130 3000 Rack EBM 2U Extended Battery Module (EBM) 2U memberikan runtime tambahan untuk UPS Eaton 9130 2000 dan 3000 rack sampai 4 EBM dapat dipasang di setiap UPS |
Power Management Connectivity | ||
---|---|---|
Network and MODBUS Card-MS Menyediakan sistem monitoring UPS jarak jauh yang akurat serta berkelanjutan |
||
Network Card-MS Menyediakan pengawasan serta pengaturan secara real time untuk UPS yang berada didalam Network anda. |
||
ConnectUPS-BD SNMP/Web Card Memungkinkan pemantauan UPS melalui Web atau SNMP |
||
Environmental Monitoring Probe Memungkinkan pengawasan jarak jauh untuk temperature, kelembaban dan dua alat contact lainnya (memerlukan Web / SNMP card) |
||
Relay Card - BD (AS/400 Compatible) Memberikan antarmuka kontak kering antara UPS Anda dan komputer yang terhubung relai, termasuk AS/400, serta berbagai aplikasi industri. |
Eaton 9PX UPS menyediakan proteksi power dengan efisiensi energi untuk ruang IT dan infrastruktur datacenter skala kecil dan menengah. Memberikan proteksi double conversion dengan pemakaian energy kurang dari 40% tetapi powernya bertambah 28%. 9PX adalah UPS yang paling sempurna untuk manager IT dan fasilitasnya yang peduli terhadap biaya energy dan mencari generasi terdepan dalam solusi power.
Parallel/Redundant Operation | ||
---|---|---|
Eaton 9PX ModularEasy 6000i | ||
Eaton 9PX ModularEasy 11000i |
Baterai | ||
---|---|---|
Eaton 9PX EBM 180V Extended battery Module untuk Eaton 9PX UPS 5KVA dan 6KVA UPS dengan rack mounting kit |
||
Eaton 9PX EBM 240V Extended battery Module untuk Eaton 9PX UPS 8KVA dan 11KVA UPS dengan rack mounting kit |
||
Eaton Supercharger 240VDC Super charger untuk 8KVA dan 11KVA models untuk waktu backup battery yang lama |
||
Eaton Battery Integration System Battery integration system untuk menempatkan beberapa EBM |
||
Eaton 1,8m kabel 180V EBM Memperpanjang jarak antara EBM dan UPS |
||
Eaton 1,8m kabel 240V EBM Memperpanjang jarak antara EBM dan UPS |
Power Management Connectivity | ||
---|---|---|
Network Card-MS Menyediakan pengawasan serta pengaturan secara real time untuk UPS yang berada didalam Network anda. |
||
Relay Card-MS Menyediakan dry-contact interface antar UPS anda dan relay yang terhubung ke computer, termasuk AS/400, dan juga berbagai penerapan industry lainnya. |
||
Network and MODBUS Card-MS Menyediakan sistem monitoring UPS jarak jauh yang akurat serta berkelanjutan |
Power Distribution and Bypass | ||
---|---|---|
Eaton HotSwap MBP 11000i 3:1 External Maintenance bypass panel untuk 6KVA, 8KVA dan 11KVA UPS |
||
Eaton HotSwap MBP 6000i External Maintenance bypass panel untuk 5KVA dan 6KVA UPS |
||
Eaton HotSwap MBP 11000i 1:1 External Maintenance bypass panel untuk 8KVA dan 11KVA UPS |
||
Eaton Transformer 11000i Isolation transformer untuk 9PX UPS 5KVA / 6KVA / 8KVA / 11KVA |
Piranti Keras Pemasangan | ||
---|---|---|
Eaton Rack kit 9PX Eaton Rail kit for 9PX UPS dan EBM |
Aksesoris | ||
---|---|---|
Eaton 9PX 6000i Power Module 3:1 | ||
Eaton 9PX 8000i Power Module 3:1 | ||
Eaton 9PX 11000i Power Module 3:1 | ||
Eaton 9PX 8000i Power Module 1:1 | ||
Eaton 9PX 11000i Power Module 1:1 |
UPS Eaton 9155 memberikan daya cadangan online premium dan runtime baterai terukur untuk infrastruktur TI dan elektrik di perusahaan, perawatan kesehatan, perbankan dan industri. Memuat runtime baterai maksimal ke dalam footprint yang sangat kecil, UPS 9155 adalah solusi lengkap pelindung daya. 9155 dapat dilengkapi dengan modul distribusi daya terintegrasi dan dapat disesuaikan yang mencakup saklar bypass maintenance.
Rating | 8 kVA | 10 kVA | 12 kVA | 15 kVA | 20 kVA | 30 kVA | ||||||||
Part number | 9155-8-S 9155-8-N |
9155-10-S 9155-10-N |
- 9155-12-N |
- 9155-15-N |
- 9155-20-N |
- 9155-30-N |
||||||||
Capacity (kVA/kilowatts) | 8 / 7.2 | 10 / 9 | 12 / 10.8 | 15 / 13.5 | 20 / 18 | 30 / 27 | ||||||||
Dimensions WxDxH (mm) | 305x702x817 | 305x702x817 | 305x702x817 | 305x702x817 | 494x762x1684 | 494x762x1684 | ||||||||
With extra runtime | 305x702x1214 | 305x702x1214 | 305x702x1214 | 305x702x1214 | - | - | ||||||||
Weight (kg) UPS without Batteries UPS with internal 1xBAT UPS with internal 2xBAT UPS with internal 3xBAT UPS with internal 4xBAT |
75 155 265 N/A N/A |
75 155 265 N/A N/A |
75 160 270 N/A N/A |
75 160 270 N/A N/A |
200 300 400 500 600 |
200 N/A 400 500 600 |
||||||||
Input connection | Hardwired | Hardwired | Hardwired | Hardwired | Hardwired | Hardwired | ||||||||
Output connection | Hardwired | Hardwired | Hardwired | Hardwired | Hardwired | Hardwired | ||||||||
*Typical runtime with 1xBAT Typical runtime with 2xBAT Typical runtime with 3xBAT Typical runtime with 4xBAT |
15 min 33 min N/A N/A |
10 min 25 min N/A N/A |
8 min 20 min N/A N/A |
5 min 15 min N/A N/A |
5 min 13 min 22 min 31 min |
N/A 7 min 13 min 20 min |
||||||||
Operational | ||||||||||||||
Nominal input voltage (Vac) |
S models: 220/230/240 Vac single phase; N models: 220/380, 230/400, 240/415 Vac three phase |
|||||||||||||
Input voltage range | 175/305V - 276/478V at 100% load, 115/200V - 276/478V at 50% load | |||||||||||||
Operating frequency | 50/60 Hz (45 to 65 Hz) | |||||||||||||
Input power factor | 0.99 | |||||||||||||
Input current distortion | 5% THD in normal network condition | |||||||||||||
Nominal output voltage | 220/230/240 VAC single phase | |||||||||||||
Output voltage regulation |
±2% static; ±5% dynamic at 100% load change, < 1 ms response time |
|||||||||||||
Overload capacity | 150% for 5 sec / 125% for 1 min (online), 1000% for 20 msec (bypass) | |||||||||||||
Efficiency | 92% with computer load; 93% with linear load | |||||||||||||
User interface | ||||||||||||||
LCD-display | Graphical LCD with blue backlight, English, German and Spanish languages, extendable | |||||||||||||
LED | 4 LED for notice and alarm | |||||||||||||
Standard communication ports |
1 x RS232 for local support, 2 x X-slot (empty); 1 x relay contact, 1 x emergency power off input, 2 x environmental input |
|||||||||||||
Optional | External battery cabinets; isolation transformer; external mechanical bypass switch; X-slot; Web/SNMP, Modbus/Jbus, relay card, RS232 port, Hot Sync card | |||||||||||||
Environmental | ||||||||||||||
Operating temperature | 0ºC to +40ºC | |||||||||||||
Storage temperature | -15ºC to +40ºC | |||||||||||||
Altitude | < 1000 m at +40ºC, < 3000 m at +25ºC | |||||||||||||
Audible noise at 1 metre | < 50 dB(A) at 1 metre | |||||||||||||
Certification | ||||||||||||||
Quality | ISO 9001; 2000 and ISO 14001:1996 | |||||||||||||
Markings | CE and GOST markings / C-Tick | |||||||||||||
Safety | IEC 62040-1-1, IEC 60950, EN 62040-1-1 | |||||||||||||
EMC | EN 50091-2 Class A, C-Tick |
Baterai | ||
---|---|---|
Eaton 9155 EBM 64 Extended Battery Module (EBM) memberikan runtime tambahan untuk UPS Eaton 9155 |
||
Eaton 9155 EBM 96 Extended Battery Module (EBM) memberikan runtime tambahan untuk UPS Eaton 9155 |
Power Management Connectivity | ||
---|---|---|
Environmental Monitoring Probe Memungkinkan pengawasan jarak jauh untuk temperature, kelembaban dan dua alat contact lainnya (memerlikan Web / SNMP card) |
||
Relay Card Memberikan antarmuka kontak kering antara UPS Anda dan komputer yang terhubung relai, termasuk AS/400, serta berbagai aplikasi industri. |
||
Modbus Card Memberikan pemantauan jaringan yang kontinu, dapat diandalkan dan akurat untuk sistem UPS melalui Building Management System (BMS). |
||
Industrial Relay Card Industrial Relay Card & Display X-Slot Card |
||
CAN Bridge Card CAN Bridge Card untuk memparalelkan unit dan/atau antarmuka RMP/RIM/SCM. x2 untuk N+1, x3 untuk N+2 |
||
Alarm Serial Card |
Power Distribution and Bypass | ||
---|---|---|
Eaton ePDU Enclosure Power Distribution Unit mendistribusikan daya ke 4 sampai 45 reseptakel dalam lingkungan rak dengan kepadatan tinggi. Arsitektur plug and play mengatur distribusi daya, menyederhanakan pengelolaan kabel dan memungkinkan Anda menambah dan mengganti peralatan TI tanpa juru listrik. |
The Eaton 9E is an online double-conversion power protection at an affordable price with compact yet robust construction. This UPS an ideal choice for industrial, medical and information technology (IT) applications and telecommunications.
Baterai | ||
---|---|---|
Eaton 9E EBM 180V | ||
Eaton 9E EBM 240V | ||
Eaton 9E EBM 480V |
Power Management Connectivity | ||
---|---|---|
Network Card-MS Menyediakan pengawasan serta pengaturan secara real time untuk UPS yang berada didalam Network anda. |
||
Relay Card-MS Menyediakan dry-contact interface antar UPS anda dan relay yang terhubung ke computer, termasuk AS/400, dan juga berbagai penerapan industry lainnya. |
||
Network and MODBUS Card-MS Menyediakan sistem monitoring UPS jarak jauh yang akurat serta berkelanjutan. |
Aegis Pro series UPS is three phase on-line double-conversion UPS designed in small footprints with input power factor correction (Input PF≥0.99) and an enhanced output power factor to 0.9. It’s the ideal solution for critical information and telecommunication systems, network services. Aegis series UPS includes dual-mains input, automatic and maintenance bypass which make the system more reliable and easy to maintenance, moreover scalable runtime with flexible built-in/external batteries for increased availability.
Eaton 93E XL UPS memberikan perlindungan sumber daya yang baik dengan kekuatan serta kepadatan energy tertinggi di industri. 93E XL mampu memberikan biaya terendah dikelasnya dengan menggabungkan footprint yang terpadu, keluwesan serta kemudahan pemasangan yang belum pernah ada sebelumnya. 93E XL sangat ideal untuk penggunaan yang membutuhkan waktu backup yang lama serta yang mengalami kendala dalam urusan ruang.
Daya | |||||
Rating | 10kVA/9kW | 15kVA/13.5kW | 20kVA/18kW | 30kVA/27kW | 40kVA/36kW |
Topologi | Konversi-ganda online UPS | ||||
Frekuensi Oprasi | 50/60 Hz (40 hingga 72 Hz) | ||||
Factor masukan daya | >0.99 tipikal | ||||
Distorsi masukan arus | ≤5% THD | ||||
Masukan elektrik | |||||
Nominal masukan tegangan | 400/230V, 4 kabel (380/415V dapat dipilih) | ||||
Tingkat tegangan input | -15%, +20% Dari angka (400V) pada beban 100% tanpa menghabiskan baterai | ||||
Keluaran elektrik | |||||
Nominal output tegangan | 400/230, 4 kabel (380/415V dapat dipilih) | ||||
Variasi tegangan output | (±1% Statis; <5% Dinamis pada perubahan beba resistif 100%, <20 ms waktu respon | ||||
Baterai | |||||
Baterai | 432V (216 Cells * 6 strings(max), Dengan baterai internal default) | ||||
Metode pengisian | ABM Cyclic Charging | ||||
Umum | |||||
Efisiensi |
Mode >98% High-efficiency Mode >94% Double-conversion |
||||
Overload | 150% untuk 1 menit, 125% untuk 10 menit,> 150% untuk 150ms | ||||
UPS bypass | Otomatis jika UPS mengalami overload atau tidak berfungsi | ||||
Parallel technology | Hot Sync® Technology | ||||
Dimensi Lebar x Diamter x Tinggi (mm) | 600 x 800 x 1876 | ||||
Cabinet rating | IP20 dengan filter debu yang bisa dicuci | ||||
Berat dengan 6 strings baterai internal |
10kVA 770kg 15kVA 770kg 20kVA 770kg 30kVA 780kg 40kVA 790kg |
||||
Komunikasi | |||||
Tampilan | Grafis LCD dengan backlight biru | ||||
LEDs | 4x LEDs untuk notifikasi dan alarm | ||||
Suara alaram | Ya | ||||
Port komunikas | (1) RS-232, (1) USB, (1) EPO | ||||
Slot komunikasi | (2) Mini-slot communication bays | ||||
Environmental | |||||
Temperatur pengoperasian |
0ºC to +40ºC Suhu baterai disarankan maksimal. +25ºC |
||||
Temperature penyimpanan | -25ºC to +55ºC Dengan baterai +15ºC to +25ºC Tanpa baterai |
||||
Tingkat kelembaban | 5–95%, Non-kondensasi | ||||
Tingkat kebisingan | 10kVA ≤55 dB(A) Pada jarak 1m 15kVA ≤55 dB(A) Pada jarak 1m 20kVA ≤55 dB(A) Pada jarak 1m 30kVA ≤62 dB(A) Pada jarak 1m 40kVA ≤62 dB(A) Pada jarak 1m |
||||
Ketinggian | <1000m at +40°C | ||||
Certifications | |||||
EMI standards | EN55022/EN55024 | ||||
Pemenuhan EMC | IEC 62040-2 | ||||
Kualitas | ISO 9001: 2000 dan ISO 14001:1996 | ||||
Communication Accessories | |||||
Network-MS | Web/SNMP Card | ||||
Modbus-MS | Web/SNMP dan Modbus Card | ||||
Relay-MS | Relay (Dry Contact) Card -DB9 Connection | ||||
Industrial Relay | Relay (Dry Contact) Card -Terminal Connection | ||||
116750224-001 | Environmental Monitor Probe (EMP) kit (harus disambungkan ke Web/SNMP Card atau Web/SNMP dan Modbus Card agar berfungsi) |
Dikarenakan produk yang terus dikembangkan, spefisifikasi bisa berubah setiap saat tanpa pemberitahuan.
Scalable Runtime * | ||
Rating Daya | Model No. | Backup Time (min) |
10kVA | 93EXL-10-2S-40M-E 93EXL-10-3S-60M-E 93EXL-10-4S-90M-E |
40 60 90 |
15kVA | 93EXL-15-3S-40M-E 93EXL-15-4S-55M-E 93EXL-15-5S-72M-E 93EXL-15-6S-92M-E |
40 55 72 92 |
20KVA | 93EXL-20-3S-27M-E 93EXL-20-4S-40M-E 93EXL-20-5S-50M-E 93EXL-20-6S-60M-E |
27 40 50 60 |
30KVA | 93EXL-30-3S-15M-E 93EXL-30-4S-24M-E 93EXL-30-5S-30M-E 93EXL-30-6S-40M-E |
15 24 30 40 |
40kVA | 93EXL-40-4S-15M-E 93EXL-40-5S-22M-E 93EXL-40-6S-27M-E |
15 22 27 |
*Catatan: Waktu backup (min) berdasarkan kondisi UPS 80% terisi dan beban pada 0,9PF
Power Management Connectivity | ||
---|---|---|
Environmental Monitoring Probe Memungkinkan pengawasan jarak jauh untuk temperature, kelembaban dan dua alat contact lainnya (memerlukan Web / SNMP card) |
||
Industrial Relay Card Industrial Relay Card & Display X-Slot Card |
||
Network Card-MS Menyediakan pengawasan serta pengaturan secara real time untuk UPS yang berada didalam Network anda. |
||
Relay Card-MS Menyediakan dry-contact interface antar UPS anda dan relay yang terhubung ke computer, termasuk AS/400, dan juga berbagai penerapan industri lainnya |
||
Network and MODBUS Card-MS Menyediakan sistem monitoring UPS jarak jauh yang akurat serta berkelanjutan |
Aegis series UPS is the high density version of three phase on-line double-conversion UPS offers high levels of reliability and protection for IT systems, telecommunication equipment and mission critical systems like small data centers, large retail stores and regional offices. Its modularized design of subsystem, dual-mains input and standard maintenance bypass make maintenance easier on site, and high overall efficiency ensures low power consumption. Moreover for increased availability, scalable runtime is available with flexible built-in/external batteries. Meanwhile optional built-in isolation transformer makes the whole system more reliable.
Eaton 93E UPS memberikan power proteksi superior pada penambahan beban yang besar disaat terbatasnya ruangan datacenter. Menawarkan solusi total biaya kepemilikan (Total cost of ownership - TCO) yang rendah melalui kombinasi antara efisiensi energi, tingkat kestabilan yang tinggi dan tampilan yang ringkas pada 93E, menjadikan solusi ideal untuk datacenter kapasitas kecil hingga menengah dan aplikasi lain yang membutuhkan proteksi power yang handal.
Power | |
Ratings | 15kVA/13.5kW, 20kVA/18kW, 30kVA/27kW, 40kVA/36kW, 60kVA/54kW, 80kVA/72kW, 100kVA/90kW, 120kVA/108kW, 160kVA/144kW, 200kVA/180kW, 300kVA/270kW, 400kVA/360kW, 500kVA/450kW |
Topology | Double-conversion online UPS |
Electrical Input | |
Nominal input voltage | 400/230V, 4 wire (380/415V selectable) |
Input voltage range | -15%, +20% from nominal (400V) at 100% load without depleting battery |
Operating frequency | 50/60 Hz (40 to 72 Hz) |
Input power factor | >0.99 typical |
Input current distortion | ≤5% THD |
Electrical Output | |
Nominal output voltage | 400/230, 4 wire (380/415V selectable) |
Output voltage regulation | ±1% Static; ±5% dynamic at 100% resistive load change, <20 ms response time |
Battery | 192 to 240 Cells (Continual selectable for 15-80kVA) 216/222/228/234/240 Cells (Selectable for 100-500kVA) |
Charging method | ABM Cyclic Charging |
General | |
Efficiency |
>98% High-efficiency mode (15-80kVA) >98.5% High-efficiency mode (100-300kVA) >99% High-efficiency mode (400-500kVA) >94% Double-conversion mode (15-300kVA) >95% Double-conversion mode (400-500kVA) |
UPS bypass | Automatic on overload or UPS failure |
Parallel technology | Powerware Hot Sync® Technology |
Dimensions W x D x H |
500 x 710 x 960 (mm) 15-20kVA (with internal battery) 500 x 710 x 1230 (mm) 30kVA (with internal battery) 500 x 710 x 1500 (mm) 40kVA (with internal battery) 600 x 800 x 1876 (mm) 60-200kVA 1600 x 820 x 1880 (mm) 300/500kVA |
Cabinet rating | IP20 with standard washable dust filters |
Weights without internal battery |
15/20kVA-72kg, 30kVA-88kg, 40kVA-120kg, 60kVA-202kg, 80kVA-245kg, 100kVA-283kg, 120kVA-311kg, 160/200kVA-457kg, 300kVA-860kg, 400kVA-970kg, 500kVA-1020kg |
Weights with internal battery | 15/20kVA-272kg, 30kVA-376kg, 40kVA-490kg |
Overload | 150% for 1 minute, 125% for 10 minutes, >150% for 150ms |
Communications | |
Display | Graphical LCD with blue backlight |
LEDs | (4) LEDs for notice and alarm |
Audible alarms | Yes |
Communication ports | (1) RS-232, (1) USB, (1) EPO |
Communication slots | (2) Mini-slot communication bays |
Environmental | |
Operating temperature |
0ºC to +40ºC Batteries recommended max. +25ºC |
Storage temperature | -25ºC to +55ºC without batteries +15ºC to +25ºC with batteries |
Relative humidity | 5–95%, non-condensing |
Audible noise | 15-20kVA≤55 dBA at 1m typical 30-40kVA ≤62 dBA at 1m typical 60-120kVA ≤65 dBA at 1m typical 160-200kVA ≤70 dBA at 1m typical 300-400kVA ≤73 dBA at 1m typical 500kVA ≤75dBA at 1m typical |
Altitude | <1000m at +40°C |
Certifications | |
EMI standards | EN55022/EN55024 |
EMC compliance | IEC 62040-2 |
Quality | ISO 9001: 2000 and ISO 14001:1996 |
Communication Accessories | |
Network-MS | Web/SNMP Card |
Modbus-MS | Web/SNMP and Modbus Card |
Relay-MS | Relay (Dry Contact) Card -DB9 Connection |
Industrial Relay | Relay (Dry Contact) Card -Terminal Connection |
116750224-001 | Environmental Monitor Probe (EMP) kit (need to plug into Web/SNMP Card or Web/SNMP and Modbus Card to work) |
System Accessories | |
Battery Cabinets & Battery Circuit Breakers (60-200kVA) | |
Maintenance Bypass Switches (MBS) (100-200kVA, standard on 15-80kVA) | |
Top Cable Entry (60-200kVA, standard on 300-500kVA) | |
System Parallel Modules (60-200kVA) | |
Dual input kit (15-80kVA) | |
IP21 hood (15-200kVA) | |
Rear Chimney (60-200kVA) |
In the interests of continuous product improvement all specifications are subject to change without notice.
Power Management Connectivity | ||
---|---|---|
Network Card-MS Menyediakan pengawasan serta pengaturan secara real time untuk UPS yang berada didalam Network anda. |
||
Relay Card-MS Menyediakan dry-contact interface antar UPS anda dan relay yang terhubung ke computer, termasuk AS/400, dan juga berbagai penerapan industri lainnya |
||
Network and MODBUS Card-MS Menyediakan sistem monitoring UPS jarak jauh yang akurat serta berkelanjutan |
ACE series UPS is on-line double-conversion UPS with built-in output isolation transformer, offering highly reliable power for most applications, especially suitable for medical system and industrial automation system. The ACE range includes single-phase input and single-phase output versions 6/10KVA and three-phase input and single-phase output versions from 10KVA to 30KVA. Its bypass dual DSP control design and high overload capability (up to 150%) make it ideal solution to protect critical devices in harsh and unstable grid environment.
High reliability
Armor series UPS 10 ~ 120KVA is intelligent three-phase online double conversion low frequency UPS with HPWM and full DSP technology, friendly man-machine interface and intelligent monitoring managment, integrating high reliability, security and maintainability to offer strong power guard for all kinds of loads, such as the IT systems, strongly inductive or capacitive loads, induction motors.
Armor series UPS 160~500KVA acquires online double conversion with full DSP technology. Its rectifier adopts three-level PWM rectifier technology based on IGBT components, realizing excellent performance of high input power factor and low input harmonic current. Its inverter also adopts PWM technology based on IGBT components, and is equipped with output isolation transformer, realizing high performance of stable voltage, stable frequency, low waveform distortion, strong load capacity and impact resistance capacity. Armor series UPS remains a high efficiency of an output power factor to 0.9, offering high quality power for all kinds of loads, especially inductive or capacitive loads in industrial applications.
Modular 25 series UPS is ideal for reliable, saving, intelligent and easy solutions. It ensure that a scalable, secure, high quality power supply is available for any critical high-density computer and IT environment applications, such as data centers and other critical loads. Modular 25 series UPS is a high-end modular UPS with latest DSP control technology and most reliable, famous brand components. It adopts a highly intelligent modular design, which mainly contains power modules, bypass module and control module, all modules support “plug & play” to simplify UPS servicing and maintenance. The available UPS power and redundancy level can expand vertically from 25 kVA / 25 kW to 125 kVA / 125 KW in one single power cabinet with flexible configuration for meeting different needs. Based on superior electrical performance, perfect hardware and software protection function, EA660 Series UPS can adapt to different grid environment and provides maximum protection and high quality power for critical loads in data centers or other important applications.
online double-conversion with DSP control
Thanks to the unity power factor to guarantee maximum real power
operation for all modules
easy installation and economic initial investment
50Hz / 60Hz auto sensing frequency
50Hz input / 60Hz output and 60Hz input / 50Hz output
Input Power Factor > 0.99, Input THDi ≤ 3%, Output THDV ≤ 5%
and redundancy technology easily set up different numbers of redundancy UPS module via LCD
40 x 12V/9AH for each module
in parallel operation, saving user’s battery cost
up to 160KVA/160KW constructed by each module 20KVA / 20KW, single charger module be equipped with 30 A charging current, 4 modules be configured maximally
and battery configuration setting, selectable battery number: 32 pcs / 34 pcs / 36pcs / 38 pcs / 40 pcs
prolong the working life of battery effectively
and mains auto restart
between key components and air duct effectively improve the system reliability
Fragile Components can be replaced easily as modules at low maintenance cost
top / bottom cable entry compatible
for hardware and software (C class lighting protection, circuit breaker, fuse, software and hardware protection), robust self detection, abundant event log for future check
5.7 inches LCD touch screen, friendly human machine interaction
Standard RS232 / USB / RS485 / Dry Contacts Communication Port
Optional SNMP communication port
MODEL |
|||
Capacity |
80 KW / 80 KVA |
||
Numbers of parallel module |
1 ~ 4 |
||
Numbers of redundancy module |
0 ~ 3 |
||
UPS power module |
20KVA / 20KW |
||
INPUT |
|||
Rated voltage |
380V/400V/415Vac |
||
Voltage range |
204 ~ 242 Vac (load ≤ 50%); |
||
Rated frequency |
50 / 60 Hz (auto-sense) |
||
Frequency range |
40 ~ 70 Hz |
||
Power factor |
≥ 0.99 |
||
Total harmonic distortion (THDI) |
≤ 3% |
||
Bypass voltage range |
Rated output voltage - 40% ~ rated output voltage + 20% (settable via LCD) |
||
OUTPUT |
|||
Voltage |
380V / 400V / 415 Vac |
||
Voltage regulation |
± 1% |
||
Frequency |
Synchronized with utility in mains mode; |
||
Power factor |
1.0 |
||
Waveform |
Pure sine wave |
||
Crest factor |
3:1 |
||
Total harmonic distortion(THDV) |
≤ 1% (linear load); ≤ 5% (non-linear load) |
||
Transfer time |
0ms |
||
Inverter overload capability |
110% ~ 130%: transfer to bypass in 10 mins; |
||
Bypass overload capability |
≤ 150%: long time running |
||
BATTERIES |
|||
DC voltage |
± 240 Vdc (options: ± 192 Vdc / ± 204 Vdc / ± 216 Vdc / ± 228 Vdc) |
||
Inbuilt battery of standard model |
40 x 12V/9Ah for each module |
||
Charging current |
1 ~ 30A / 60A (settable via LCD) |
||
SYSTEM |
|||
Efficiency |
≥ 94% |
||
Display panel |
5.7 Inches LCD touch screen |
||
Alarm |
Battery mode, low battery, fans fault etc. |
||
EMI |
EN62040-2 |
||
EMS |
IEC61000-4-2 (ESD) |
||
COMMUNICATIONS |
|||
RS232 / RS485 / USB / dry contacts (standard) |
Supports Windows® 98/2000/2003/XP/Vista/2008/7/8/10 |
||
SNMP (option) |
Power management from SNMP manager and web browser |
||
OTHERS |
|||
Humidity |
0 ~ 95% RH @ 0 ~ 40°C (non-condensing) |
||
Noise level |
≤ 60dB |
||
Module dimensions (mm) WxDxH |
482x590x131 |
||
Module weight |
28kg / power module, 27kg / charger module, 7kg / monitoring module |
||
UPS dimensions (mm) WxDxH |
600x1000x1600 |
||
UPS packaged dimensions (mm) WxDxH |
700x1070x1760 |
||
UPS Net/Gross weight (kg) |
225 / 245 |
||
Input / output / bypass breaker |
Yes |
UPS Eaton 93PR adalah UPS modular berkelas dunia, mudah disesuaikan skala penggunaannya, dan berkemampuan hot-swap. Biaya kepemilikan total paling rendah, dan ketersediaan paling maksimal menetapkan standar baru dalam hal skalabilitas, ketangguhan, keamanan, dan efisiensi. Efisiensi terdepan di industri melampaui 96% dalam mode konversi ganda, dan mencapai efisiensi puncak sebesar 99% dengan teknologi ESS dari Eaton. Dibekali dengan solusi perangkat lunak cerdas berkelas dunia untuk pemantauan dan pengelolaan, Eaton 93PR menjadi jawaban pasti untuk menjamin kelangsungan aplikasi-aplikasi penentu bisnis Anda.
93PR menawarkan efisiensi konversi ganda tertinggi di pasaran, yakni di atas 96%.
VMMS dapat mengoptimalkan tingkat beban modul daya dalam satu UPS 93PR atau dalam sistem paralel, yakni dengan menahan kapasitas UPS ekstra. Ini tidak saja menghasilkan efisiensi besar pada tingkat daya yang rendah, tetapi juga efisiensi optimal di semua tingkat beban.
Energy Saver System memungkinkan efisiensi > 99% di seluruh rentang operasi UPS. Dalam ESS, beban ditenagai dengan aman melalui jalur bypass statis lengkap dengan konversi ganda yang bisa sewaktu-waktu digunakan dengan waktu transisi 2 milidetik apabila terjadi ketidaknormalan sumber suplai daya. Dalam mode operasi ESS, beban dilindungi oleh penahan lonjakan.
Modul daya 93PR dapat diganti atau ditambah selagi modul lain terus melindungi beban. Dengan demikian, tidak perlu lagi melakukan bypass ketika ingin mengganti atau meng-upgrade modul (MTTR: 0 menit). Penggantian dan upgrade (N+1) biasanya memerlukan waktu kurang dari 10 menit.
93PR menyediakan akses informasi status secara detail melalui layar sentuh LCD besar berukuran 7” yang mudah digunakan. Dengan antarmuka grafis LCD dari 93PR, Anda dapat memantau statistik penghematan listrik, durasi baterai, pelacakan pemadaman listrik, profil beban, dan banyak lagi. Lampu batang LED berwarna hijau/kuning/merah membuat status sistem dapat dipantau dari jauh di dalam pusat data.
Algoritme pengisian daya yang unik membuat masa pakai baterai jauh lebih panjang jika dibandingkan dengan metode pengisian daya biasa. Uji baterai otomatis memastikan segala kerusakan pada baterai terdeteksi, dan blok yang gagal dapat diganti tepat waktu. Data kondisi baterai selalu dapat dilihat dari layar tampilan. Karena dapat memonitor kondisi baterai dan riwayat data pengujian, pemeliharaan sistem pun dapat direncanakan dan dijadwalkan lebih matang jauh-jauh hari.
General | ||||||||
UPS output power rating (1.0 p.f.) | 25, 50, 75, 100, 125, 150, 175, 200kW | |||||||
Efficiency in double conversion mode | > 96% | |||||||
Efficiency in Energy Saver System (ESS) | > 99% | |||||||
Static bypass rating | 200kW | |||||||
External paralleling | up to 4 units with HotSync technology | |||||||
UPS topology | Double conversion | |||||||
UPS degree of protection | IP20 | |||||||
Acoustic noise at 1 m, in 25 °C ambient temperature | < 70 dBA in double conversion < 55 dBA in ESS |
|||||||
Altitude (max) | 1000m above sea level at 40 °C. Maximum 2000m with 1% derating per each add. 100 m | |||||||
Input | ||||||||
Rated input voltage | 220/380 V, 230/400 V, 240/415 V 50/60 Hz | |||||||
Voltage tolerance - Rectifier input | 187 to 276 V | |||||||
Voltage tolerance - Bypass input | rated voltage -15% / +10% | |||||||
Rated input frequency Frequency tolerance |
50 or 60 Hz, user configurable 40 to 72 Hz |
|||||||
Input wiring | 3 phase + neutral | |||||||
Input power factor at 100% load | > 0.99 | |||||||
Input ITHD | < 3% | |||||||
Rated input r.m.s current | 25kW | 50kW | 75kW | 100kW | 125kW | 150kW | 175kW | 200kW |
380V | 40 A | 80 A | 120 A | 159 A | 199 A | 239 A | 278 A | 318 A |
400V | 38 A | 76 A | 114 A | 151 A | 189 A | 227 A | 264 A | 302 A |
415V | 37 A | 73 A | 110 A | 146 A | 182 A | 219 A | 255 A | 291 A |
Soft start capability | Yes | |||||||
Internal backfeed protection | Yes | |||||||
Output | ||||||||
Output wiring | 3 phase + neutral | |||||||
Rated output voltage rating | 220/380 V, 230/400 V, 240/415 V, configurable | |||||||
Total voltage harmonic distortion | < 1% (100% linear load); < 5% (100% non-linear load) | |||||||
Output power factor | 1.0 | |||||||
Permitted load power factor | 0,8 lagging - 0,8 leading | |||||||
Overload on inverter | 10 min 102-110%; 60 sec 111-125%; 10 sec 126-150%; 300 ms > 150%. | |||||||
Overload on bypass | Continuous < 125%, 20 ms 1000% | |||||||
Battery | ||||||||
Battery type | 12V, VRLA | |||||||
Charging method | ABM technology or Float | |||||||
Temperature compensation | Optional | |||||||
Battery nominal voltage (VRLA) | 480 V | |||||||
Battery quantity | 36 to 44 blocks. Default is 40 blocks | |||||||
Charge current limit | Default 5A, configurable maximum 25A per UPM | |||||||
Battery start capability | Yes | |||||||
Communications | ||||||||
Minislot | 3 communication bays | |||||||
Network/SNMP interface | Yes, optional | |||||||
Serial ports | Built-in host and device USB | |||||||
Standard connectivity ports | Mini-slot ports for optional cards, Device USB and Host USB, RS-232 service port, relay output, 5 building alarm inputs and a dedicated EPO, Web and SNMP card | |||||||
Accessories | ||||||||
MiniSlot connectivity (Web/SNMP, ModBus/Jbus, Relay) External Battery Cabinet(EBC) Parallel Tie Cabinet(PTC) External Maintenance Bypass Switches(EMBS) External Battery Cabinet Breaker(EBCB) |
||||||||
Compliance with standards | ||||||||
Safety | IEC 62040-1 | |||||||
EMC | IEC 62040-2 | |||||||
Performance | IEC 62040-3 | |||||||
Mechanical | ||||||||
Weight without UPM | 368kg nett | |||||||
25kW UPM Weight | 28kg nett | |||||||
UPS dimension (W x D x H) | 603 x 1013 x 2050 mm |
Due to continuous product improvement programmes, specifications are subject to change without notice.
Modular 50 series UPS is redundant, scalable, 3 – Phase UPS power protection system with on-line double-conversion and full DSP control technology. Its hot-swappable and flexible power module configuration makes the capacity scalable from 50 KVA up to 800 KVA, and the system capacity can be expanded to 2400 KVA by advanced “N+X” wireless parallel and redundancy technology. All internal modules (control module, power module and bypass module) are modularly designed and hot-swappable, assuring system compactness, reliability and easy maintenance.
105% ~ 110% for 60 minutes, 110% ~ 125% for 10 minutes, 125% ~ 150% for 1 minute
Modular 50 is featured with high power density of 50 KVA / 3U power module
online double-conversion with DSP control
Thanks to the unity power factor to guarantee maximum real power
operation for all modules
easy installation and economic initial investment
50Hz / 60Hz auto sensing frequency
50Hz input / 60Hz output and 60Hz input / 50Hz output
Input Power Factor > 0.99, Input THDi ≤ 3%, Output THDV ≤ 5%
and redundancy technology easily set up different numbers of redundancy UPS module via LCD
40 x 12V/9AH for each module
in parallel operation, saving user’s battery cost
up to 160KVA/160KW constructed by each module 20KVA / 20KW, single charger module be equipped with 30 A charging current, 4 modules be configured maximally
and battery configuration setting, selectable battery number: 32 pcs / 34 pcs / 36pcs / 38 pcs / 40 pcs
prolong the working life of battery effectively
and mains auto restart
between key components and air duct effectively improve the system reliability
Fragile Components can be replaced easily as modules at low maintenance cost
top / bottom cable entry compatible
for hardware and software (C class lighting protection, circuit breaker, fuse, software and hardware protection), robust self detection, abundant event log for future check
5.7 inches LCD touch screen, friendly human machine interaction
Standard RS232 / USB / RS485 / Dry Contacts Communication Port
Optional SNMP communication port
MODEL |
|||
Capacity |
160 KW / 160 KVA |
||
Numbers of parallel module |
1 ~ 8 |
||
Numbers of redundancy module |
0 ~ 7 |
||
UPS power module |
20KVA / 20KW |
||
INPUT |
|||
Rated voltage |
380V/400V/415Vac |
||
Voltage range |
204 ~ 242 Vac (load ≤ 50%); |
||
Rated frequency |
50 / 60 Hz (auto-sense) |
||
Frequency range |
40 ~ 70 Hz |
||
Power factor |
≥ 0.99 |
||
Total harmonic distortion (THDI) |
≤ 3% |
||
Bypass voltage range |
Rated output voltage - 40% ~ rated output voltage + 20% (settable via LCD) |
||
OUTPUT |
|||
Voltage |
380V / 400V / 415 Vac |
||
Voltage regulation |
± 1% |
||
Frequency |
Synchronized with utility in mains mode; |
||
Power factor |
1.0 |
||
Waveform |
Pure sine wave |
||
Crest factor |
3:1 |
||
Total harmonic distortion(THDV) |
≤ 1% (linear load); ≤ 5% (non-linear load) |
||
Transfer time |
0ms |
||
Inverter overload capability |
110% ~ 130%: transfer to bypass in 10 mins; |
||
Bypass overload capability |
≤ 150%: long time running |
||
BATTERIES |
|||
DC voltage |
± 240 Vdc (options: ± 192 Vdc / ± 204 Vdc / ± 216 Vdc / ± 228 Vdc) |
||
Inbuilt battery of standard model |
40 x 12V/9Ah for each module |
||
Charging current |
1 ~ 30A / 60A (settable via LCD) |
||
SYSTEM |
|||
Efficiency |
≥ 94% |
||
Display panel |
5.7 Inches LCD touch screen |
||
Alarm |
Battery mode, low battery, fans fault etc. |
||
EMI |
EN62040-2 |
||
EMS |
IEC61000-4-2 (ESD) |
||
COMMUNICATIONS |
|||
RS232 / RS485 / USB / dry contacts (standard) |
Supports Windows® 98/2000/2003/XP/Vista/2008/7/8/10 |
||
SNMP (option) |
Power management from SNMP manager and web browser |
||
OTHERS |
|||
Humidity |
0 ~ 95% RH @ 0 ~ 40°C (non-condensing) |
||
Noise level |
≤ 60dB |
||
Module dimensions (mm) WxDxH |
482x590x131 |
||
Module weight |
28kg / power module, 27kg / charger module, 7kg / monitoring module |
||
UPS dimensions (mm) WxDxH |
600x1000x2000 |
||
UPS packaged dimensions (mm) WxDxH |
700x1070x2160 |
||
UPS Net/Gross weight (kg) |
290 / 310 |
||
Input / output / bypass breaker |
Yes |
138-485Vac ultra-wide input voltage range, suitable for the worst power grid
for modules, elimination of the single point of failure
for key components in case of power supply interruption
up to 96.5% at most frequently-used load rate, reducing power consumption of UPS and cooling efficiency
ensures efficient UPS operation
Hot swappable power module, bypass module and control module, simple maintenance and expansion in 5 minutes
for UPS, PDU and batteries, elimination of manual routing inspection
MODEL |
|||
Rated capacity |
125KW / 125KVA |
||
Numbers of power modules |
5 |
||
MAINS INPUT |
|||
Input wiring |
3Ph+N+PE |
||
Rated voltage |
380/400/415Vac |
||
Voltage range |
138 ~ 485Vac |
||
Input frequency |
40 ~ 70Hz |
||
Total harmonic distortion |
THDi < 3% for linear load |
||
Input power factor |
0.99 |
||
BYPASS INPUT |
|||
Input wiring |
3Ph+N+PE |
||
Rated voltage |
380/400/415Vac |
||
Input frequency |
50/60 ±6Hz |
||
BATTERIES |
|||
Rated voltage |
360~480Vdc |
||
OUTPUT |
|||
Output wiring |
3Ph+N+PE |
||
Voltage |
380/400/415Vac ±1% |
||
Frequency |
Tracking the bypass input (Normal mode) ; |
||
Waveform |
Sine wave (THDv < 1% for linear load) |
||
Output power factor |
1 |
||
Overload capacity |
Inverter: 110% overload for 60 minutes ; |
||
Efficiency |
Up to 96.5% |
||
Environment |
|||
Operating temperature |
0 ~ 40°C |
||
Strong temperature |
-40 ~ 70°C |
||
Relative humidity |
0% ~ 95% (No condensing) |
||
Operating altitude |
0 ~ 1000m. Above 1000m, derating rate based on EN/IEC 62040-3 |
||
Others |
|||
Dimensions (H x W x D) (mm) |
2000 x 600 x 850 |
||
Weight |
279kg |
||
Certifications |
EN/IEC 62040-1 ; EN/IEC 62040-2 ; EN/IEC 62040-3 ; CE ; CB ; RoHS ; REACH ; WEEE ; etc |
||
Communications |
Dry contacts, RS485, SNMP |
with strong load capacity
and easy scalability with all hot-swappable module design
Keep high efficiency operation at low load rate: 96% at 40% rated load and 95% at 20% rated load
of 50 KVA / 3U power module
easy installation and saving investment
Input power factor > 0.99, THDi < 3%, environment friendly and high-efficiency and energy-saving
50 Hz / 60 Hz frequency auto-sense, adapt to all kind of grid
improves generator matching up to 1:1.1
50 Hz input / 60 Hz output and 60 Hz input / 50 Hz output
enable UPS to operate efficiently at low load rate
support 4 units in parallel
Share battery pack in parallel operation, saving user’s battery cost
and battery configuration setting, battery number 30 ~ 46 pcs selectable
Intelligent charge / discharge management and float charging voltage temperature compensation, extending battery lifespan
and utility self boot
easy debugging and test on site
30% load can be driven when 2 fans fail and 50% load when 1 fan fails
top / bottom cable entry compatible
robust self-diagnostic function, and abundant event log for check
7 inches LCD touch screen, friendly human-machine interface
supports RS485 and dry contacts
MODEL |
|||
Rated capacity |
180KW / 200KVA |
||
Numbers of power modules |
4 |
||
Rated capacity of power module |
50KVA |
||
INPUT |
|||
Input wiring |
3Ph+N+PE |
||
Rated voltage |
380/400/415Vac |
||
Voltage range |
138 ~ 485 Vac (305 ~ 485 Vac without power downgrading; |
||
Input frequency |
40 ~ 70Hz |
||
Power factor |
≥ 0.99 |
||
Current distortion |
< 3% |
||
BATTERIES |
|||
Battery voltage |
± 240 Vdc (± 180, ± 192, ± 204, ± 216, ± 228, ± 252, ± 264, ± 276 selectable) |
||
Number of battery |
40 pcs12 V batteries (30 / 32 / 34 / 36 / 38 / 42 / 44 / 46 pcs selectable) |
||
OUTPUT |
|||
Output wiring |
3Ph+N+PE |
||
Rated voltage |
380 / 400 / 415 Vac ± 1% |
||
Frequency |
Synchronized with utility in mains power mode |
||
Power factor |
0.9 |
||
Voltage distortion |
≤ 1% with liner load / ≤ 3% with non-linear load |
||
Crest factor |
3:1 |
||
Inverter overload capacity |
105% < load ≤ 110%: transfer to bypass in 60 mins |
||
Bypass overload capacity |
Load ≤ 135% for long term; < 1000% load for 100ms |
||
SYSTEM |
|||
Efficiency |
96% |
||
Max. number of parallel |
4 units |
||
Transfer time |
0ms |
||
Protection |
Short circuit protection, overload protection, over-temperature protection, battery low voltage protection, output over/low voltage protection, fans failure protection etc. |
||
Communications |
RS485, dry contacts, SNMP |
||
Display |
7 inches LCD touch screen |
||
OTHERS |
|||
Operating temperature |
0 ~ 40°C |
||
Storage temperature |
-40°C ~ 70°C |
||
Humidity |
0 ~ 95% (non-condensing) |
||
Altitude |
≤ 1000m. Above 1000m, derating 1% for each additional 100m |
||
Protection level |
IP20 |
||
Noiselevel at 1 m |
< 65 dB |
||
Cabinet dimensions (WxDxH) (mm) |
600x850x2000 |
||
UPS module dimensions (WxDxH) (mm) |
442 x 620 x 130 |
||
Cabinetweight (kg) |
233 |
||
UPS module weight (kg) |
32 |